Analog Output Wiring (4-20 Ma, 1-5 Vdc) - Siemens Moore 353 User Manual

Process automation controller
Table of Contents

Advertisement

UM353-1
3. Crimp-On Connector - Insert the resistor lead and any signal wiring into the
connector until the wire ends are visible at the pin end of the connector.
Use a standard electrical connector crimp tool to crimp the connection. Be
certain that all resistor leads and signal input wires are inserted in the
connector before crimping.
4. Loosen the two terminal screws using a straight blade screwdriver with a 1/8" (3 mm) blade width. Insert
wires, resistor leads, or a crimp-on connector pin into the two openings in the side of the connector adjacent to
the selected terminal numbers.
5. Check that all involved components and station wiring are fully inserted and carefully tighten the screws to 5
in. lbs. Do not over tighten.
6. Repeat steps 1-5 for each 4-20 mA, 1-5 Vdc and millivolt input.
7. Carefully dress resistors and wiring so that excessive stress is not placed on a component, wire, or connection.

8.4.3 Analog Output Wiring (4-20 mA, 1-5 Vdc)

Analog output functions blocks are AOUT1, AOUT2, and AOUT3. Figure 8-12 shows connections for an external
device that accepts 4-20 mA. For an external device that needs 1-5 Vdc, see Figure 8-13. Refer to Section 8.4.2 for
wiring guidelines.
FIGURE 8-12 Analog Output AOUT 1, Current Output
Station Common
FIGURE 8-13 Analog Output AOUT1, Voltage Output
March 2003
Model 353
Rear Terminals
Station Common
6
4-20 mA
+
17
_
18
MG000661
Common Ground Bus
Earth
Note: See Table 8.1 for AOUT2 terminals.
Ground
Model 353
Rear Terminals
6
1-5 Vdc
+
17
_
18
250
MG000661
Common Ground Bus
Earth
Note: See Table 8.1 for AOUT2 terminals.
Ground
Signal Input Wire
Range Resistor
Model 760
Valve Positioner,
+
Model 773
I/P Transducer,
_
or Other 4-20 MA
Device
Model 363 Recorder
+
or Other 1-5 Vdc
_
Device
Installation
Crimp-On
Connector
8-15