Remove filler panels

Install a DS60 shelf into the rack

Install an FS25 shelf into the rack
Remove filler panels
The front space into which you will install the shelf is usually covered by a filler panel. If one or more filler panels cover the space
where you want to install the shelf, use this procedure to remove each panel.
Steps
1. On the filler panel, slide the left and right securing tabs to the open position (towards the center of the panel).
2. Remove the filler panel from the cabinet.
Install a DS60 shelf into the rack
Complete the following steps to install a DS60 expansion shelf.
CAUTION:
If the top of the shelf is installed above 32U high, a ladder is required to replace disk drives in DS60
shelves.

Installing rails

About this task
Install the rails from the front of the cabinet where you will install the shelf. The 4U rack includes inner rails that slide into the
cabinet rail assembly.
CAUTION:
Exercise care when installing the short rails. Exposed metal edges may be sharp and could damage
cabling or cause injury to personnel.