 How to count I/O numbers for units that have both inputs and outputs
In the case of a unit that has both inputs and outputs (e.g. mixed input/output units, intelligent
units), input numbers and output numbers start with the same value.
E.g. If input numbers for a mixed input/output unit are X100 to X11F, the unit's output
numbers are set at Y100 to Y11F.
 I/O numbers allocated to the CPU unit
A fixed area is allocated to the COM port and the ET-LAN port.
When the number of occupied input words is different from the number of
occupied output words, the larger number is allocated to the unit.
For using the user connections 17 to 216 by extending the number of user
connections with the built-in ET-LAN in the CPU unit, 26-word area (WX11 to
WX36/WY11 to WY36) is used as a flag for confirming the communication
instruction SEND/RECV. Change the starting number of the CPU unit or
another unit not to overlap I/O maps.
The starting numbers of I/O contacts of each unit including the CPU unit
can be changed by the setting of tool software.
3.1 Basics of I/O Allocation