Specifications
WS10 (Logging trace control relays: For LOG0)
Device
number
SR100
Logging trace execution
SR101
SD card logging execution
SR102
Logging trace completed
SR103
Logging excessive speed relay
SR104
Buffer overflow
SR105
Logging trace error
SR106
No SD card free space
SR107
Device and trigger setting error
SR108
Tracing stop trigger monitor
SR109
Trace data acquisition complete
SR10A
(Not used)
- SR10F
8-14
Name
Turns on when the logging trace is performed. Other relays in
LOGn turns off while this relay turns on. Storing data in the
buffer memory is executed while this relay turns on.
Turns on when writing files to a SD card becomes enabled
after the logging trace execution relay turned on (buffer
logging was enabled).
Turns on after the completion of file writing when stopping the
logging trace is requested or it is automatically stopped.
Turns on when the buffer logging speed exceeds the writing
speed to a SD memory card in logging operations. Turns on
when the number of data stored previously and the number of
data stored this time increase.
Turns on at the timing of buffer logging, and turns off at the
timing of buffer logging or the end of scan.
Turns on when the buffer memory has been exhausted. At
that time, new data cannot be stored.
The value of the buffer overflow counter SD120 is
incremented (+1). In that case, writing to SD card does not
stop.
Turns off at the end of scan when buffer vacancy occurs while
writing to a SD memory card is performed. The buffer
overflow counter SD120 is cleared to 0.
After buffer vacancy occurred, data logging is executed at the
timing of logging to the buffer.
Turns on when an error is detected during the logging trace
and stops the logging trace.
Turns on when an error is detected during the logging trace
and stops the logging trace.
Turns on when an error is detected in setting values during
the startup operation. The error relay SR105 also turns on. At
that time, the execution relay SR100 does not turn on as the
logging trace function cannot be started.
Monitors a registered trace stop trigger when executing
tracing. Turns on when conditions are met.
Turns on after logging data for a specified number of times
after detecting the tracing stop trigger during the execution of
trace.