When to Keep the AC Wire Map Test Off

Turn off the AC wire map test when you do not do tests
through PoE devices. The test can increase the time taken for
an Autotest.
Turn off the AC wire map test when you select TIA Cat 6 or 6A
or Class E or E
always fail with these limits because PoE devices are not
designed to operate with protocols above 1000BASE-T. To use
those limits on a link that has PoE, do not do tests through
the PoE device.
Turn off the AC wire map test if the PoE device supplies power
on pairs 4,5 and 7,8. In those devices, the inputs and outputs
are fully isolated on those pairs. To do tests through those
devices, use a PoE test limit such as POE 2-Pair Cat 6 Perm.
Link. The PoE limits are in the Application group on the TEST
LIMIT screen.

How to Do an Autotest Through a PoE Device

Turn on the AC Wire Map test.
1
Make sure that the other settings shown on the home screen
2
are correct.
Connect to the cabling as shown in Figure for a permanent
3
link or Figure 72 for a channel
Make sure that the PoE device is turned off.
4
Do an Autotest as described on page 90.
5
160