Use the Display to Control the Main Tester's Light Source

Clean and inspect all connectors you will use.
1
Connect the tester's output port to the power meter.
2
If your tester has a CertiFiber Pro Quad module installed, make
sure you connect the fiber to the correct output port.
On the home screen tap TOOLS, tap Power Meter / Light
3
Source, then select settings for the source. See Figure 127.

Use the Module's Button to Control the Light Source

The button next to the VFL port puts the output port in auto
wavelength mode. In this mode, the port transmits both
wavelengths (850 nm and 1300 nm or 1310 nm and 1550 nm). The
signal includes identifiers that tell the meter when to measure
power at each wavelength. Use this mode only with a CertiFiber
Pro or SimpliFiber Pro power meter.
The remote source always operates in auto
wavelength mode.
Clean and inspect all connectors you will use.
1
Connect the tester's output port to the power meter.
2
If your tester has a CertiFiber Pro Quad module installed, make
sure you connect the fiber to the correct output port.
Hold down the button adjacent to the VFL port for 3 seconds.
3
On CertiFiber Pro Quad modules, to turn on the singlemode
source, press the button again.
On a main tester used as a source, you can use the POWER
METER / LIGHT SOURCE screen to select different settings for
the source. See Figure 127.
300
Note