Frico Thermocassette HP Series Manual page 9

Hide thumbs Also See for Thermocassette HP Series:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 9
Area of use
The heating panel is intended for the heating
of rooms requiring free walls. The panel
can be used for complete heating, or as an
additional heater (e.g. over a reception desk
or other work place).
There are two ratings: 300 W and 600 W.
The heating panel provides mainly radiation
heating. This implies that to obtain the
same experienced temperature it is possible
to reduce the air temperature in the room,
which saves energy.
Because of the low surface temperature,
max 100°C, the heating panel is suitable
for rooms with relatively low ceiling height.
Thanks to the location, the panel is protected
from any physical contact or damage. There
is no risk of being burned.
Design
The heating panels are available for 230 V and
are approved by TÜV in two versions:
1. Ceiling model: Intended as lay-in panel for
exposed grid. With cord, socket and plug,
which ensures simple extended connection
(max 2100 W from one wall socket).
2. Universal model in flush-proof design
(IP55): With better protection against
water. Delivered with cable without plug
and brackets.
One or more units have to be connected to
power line with a differential circuit breaker
rated at 30 mA. The cable section has to be at
least 1,5 mm
.
2
Units with cable and plug can be inter-
connected using the sockets on the back of
the heaters. The maximum power in inter-
connection is 2100 W.
If the units are to be extra insulated, then
this insulation must not exceed a value of
R=5 m
K/W.
2
Thermocassette HP
Mounting and assembly instruction
Mounting
Integrated in ceiling (put in exposed grid)
See fig. 2
1. Lateral distance to wall shall be at least
50 mm.
2. The heater(s) should only be wired by a
competent electrician, and in accordance
with existing national regulations. The
appliance should be preceded by an all
pole switch in accordance with existing
regulations (not applicable to versions with
a cord and plug).
3. Place the cassette in the required ceiling
square. Minimum design height "H" for
dismounting, T-profile 32x15: 150 mm,
T-profile 38x24: 200 mm. NOTE! Avoid
fixing vertical bars in the T-profile where a
heating panel is to be installed. The panel
fills out the whole square.
4. Connect the panel.
5. The second last page in this mounting
instruction is to be filled out and fixed
adjacent to the distribution board and it
has to contain (drawing) the locations of
the heating units.
Bracket mounting
See fig. 3
1. Mounting height above floor shall be at
least 1,8 m, and lateral distance to wall at
least 50 mm. When mounting in gypsum
board, make sure that the mounting
brackets are anchored in the beam behind.
During long-term high temperatures the
strength of the board is reduced.
2. The heater(s) should only be wired by a
competent electrician, and in accordance
with existing national regulations. The
appliance should be preceded by an all
pole switch in accordance with existing
regulations (not applicable to versions with
a cord and plug).
3. Measure, drill and screw the two loose
brackets to the ceiling. Do not tighten the
screws yet. It is important that the holes
come at right angles, cross measure. (fig.
3A)