Siemens SIMATIC S7-400 Manual page 95

Cpu
Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Bit
6
0:The bit is always set to "0".
7
1:The DP slave is disabled; in other words, it has been removed from cyclic processing.
Table 5-16
Structure of station status 3 (Byte 2)
Bit
0
to
0:The bits are always set to "0".
6
7
1:
Master PROFIBUS Address
The master PROFIBUS address diagnostic byte contains the DP address of the DP master
that:
● Assigned parameters to the DP slave and
● has read and write access to the DP slave
Table 5-17
Structure of the master PROFIBUS address (byte 3)
Bit
0 to 7
DP address of the DP master that configured the DP slave and that has read and write access to the DP
slave.
FF
: DP slave has not been assigned parameters by any DP master.
H
S7-400 Automation System, CPU Specifications
Manual, 10/2006, 6ES7498-8AA04-8BA0
There are more diagnostic messages than the DP slave can store.
The DP master cannot enter all the diagnostic messages sent by the DP slave in its
diagnostic buffer.
5.1 CPU 41x-3 PN/DP as DP master / DP slave
Meaning
Meaning
Meaning
PROFIBUS DP
5-21