PROFIBUS DP
5.1 CPU 41x-3 PN/DP as DP master / DP slave
Data Transfer Via an Transfer Memory
As a DP slave the CPU 41x makes an transfer memory available to PROFIBUS DP. Data
transfer between the CPU as DP slave and the DP master always takes place via this
transfer memory. Configure the following address areas: 244 bytes per input / output with a
maximum of 32 bytes per module.
That is, the DP master writes its data to these transfer memory address areas, the CPU
reads these data in the user program, and vice versa.
Figure 5-2
Address Areas of the Transfer Memory
Configure the input and output address areas in
● You can configure up to 32 input and output address areas.
● Each of these address areas can be up to 32 bytes in size.
● You can configure a maximum of 244 bytes of inputs and 244 bytes of outputs in total.
An example for the configuration of the address assignments of the transfer memory is
provided in the table below. You will also find this in the online help for STEP 7 configuration.
Table 5-7
1
2
:
32
5-12
DP master
Intermediate
memory
in the I/O
address area
PROFIBUS
Transfer memory in the CPU 41x as DP slave
Configuration example for the address areas of the transfer memory
Type
Master address
E
222
O
0
Address areas in the
DP master CPU
CPU 41x as DP Slave
I/O
STEP 7
Type
Slave address
O
310
E
13
Address areas in the
DP slave CPU
I/O
:
Length
Unit
2
Byte
10
Word
These parameters of the address areas
must be the same for the DP master and
DP slave
S7-400 Automation System, CPU Specifications
Manual, 10/2006, 6ES7498-8AA04-8BA0
Consistency
Unit
Total length