Siemens SIMATIC S7-400 Manual page 130

Cpu
Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Cycle and Response Times of the S7-400
9.2 Cycle Time Calculation
Process Image Updating
The table below shows the CPU times for process image updating (process image transfer
time). The times listed in the table are "ideal values" that may be increased by the
occurrence of interrupts and by CPU communications.
The transfer time for process image updating is calculated as follows
C + portion in central controller (from row A of the following table)
The tables below show the individual portions of the transfer time process image updating
(process image transfer time). The times listed in the table are "ideal values" that may be
increased by the occurrence of interrupts and by CPU communications.
Table 9-3
Portions of the process image transfer time
Portions
n = number of bytes in the process image
C Base load
O In the central rack
*)
B
In the expansion rack with local connection
C In the expansion rack with remote connection
Reading
Writing
D
In the DP area for the integrated DP interface
1
D
In the DP area for the external DP interface
2
CP 443-5 extended
E
Consistent data in the process image for the
1
integrated DP interface
E
Consistent data in the process image for the external
2
DP interface (CP 443-5 extended)
F
In the PN/IO area for the integrated interface
1
F
In the PN/IO area for the external interface
2
CP 443-1 EX 41
In the case of I/O modules that are plugged into the central rack or an expansion rack,
*
the specified value contains the runtime of the I/O module
Measured with the IM 460-3 and IM 461-3 with a connection length of 100 m
**
9-4
+ portion in the expansion rack with local connection (from row B)
+ portion in the expansion rack with remote connection (from row C)
+ portion over integrated DP interface (from row D)
+ portion of consistent data over integrated DP interface (from row E1)
+ portion of consistent data over external DP interface (from row E2)
__________________________________________________________________
= Transfer time for the process image update
*)
*) **)
CPU 414
7 µs
n * 1.8 µs
n * 5.5 µs
n * 12 µs
n * 11 µs
n * 0.5 µs
n * 2.5 µs
n * 0.45 µs
n * 2.0 µs
n * 5.6 µs
n * 3.1 µs
S7-400 Automation System, CPU Specifications
CPU 416
5 µs
n * 1.75 µs
n * 5.4 µs
n * 12 µs
n * 11 µs
n * 0.45 µs
n * 2.4 µs
n * 0.3 µs
n * 2.0 µs
n * 5.6 µs
n * 2.8 µs
Manual, 10/2006, 6ES7498-8AA04-8BA0