Reference setting for the CPU communication
load
Number of remote interconnecting partners
Number of master/slave functions
Total of all master/slave connections
Data length of all incoming master/slave
connections, max.
Data length of all outgoing master/slave
connections, max.
Number of device-internal and PROFIBUS
interconnections
Data length of the device-internal and PROFIBUS
interconnections, max.
Data length per connection, max.
Remote interconnections with acyclic
transmission
Remote interconnections with cyclic transmission
HMI variables via PROFINET (acyclic)
S7-400 Automation System, CPU Specifications
Manual, 10/2006, 6ES7498-8AA04-8BA0
10.3 Technical Specification of the CPU 416-3F PN/DP; (6ES7416-3FR05-0AB0)
Scan rate: Scan interval, min.
Number of incoming
interconnections
Number of outgoing
interconnections
Data length of all incoming
interconnections, max.
Data length of all outgoing
interconnections, max.
Data length per connection,
(acyclic interconnections), max.
Transmission frequency:
Minimum transmission interval
Number of incoming
interconnections
Number of outgoing
interconnections
Data length of all incoming
interconnections, max.
Data length of all outgoing
interconnections
Data length per connection,
(acyclic interconnections), max.
Update HMI variables
Number of stations that can be
logged on for HMI variables
(PN OPC/iMAP)
Number of HMI variables
CPU and firmware version
PROFINET CBA
20%
32
150
6000
65000 bytes
65000 bytes
1000
16000 bytes
2000 bytes
200 ms
500
500
16000 bytes
16000 bytes
1400 bytes
1 ms
300
300
4800 bytes
4800 bytes
250 bytes
500 ms
2*PN OPC / 1* iMAP
1000
Technical specifications
10-33