olympia electronics GR-577/L/15/ST/WP Quick Start Manual

olympia electronics GR-577/L/15/ST/WP Quick Start Manual

Waterproof self testing maintained emergency luminaire signs (for tunnels ) with leds

Advertisement

Quick Links

EMERGENCY LUMINAIRE SIGNS (for tunnels ) WITH LEDs
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-Cd)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
LIGHT SOURCE INTENSITY (230V AC/emerg.)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used in places where
emergency luminaires are needed.
E a c h l u m i n a i r e m u s t b e p e r m a n e n t l y
connected to mains power supply. In normal
operation (L1 connected to L) the led strip
lights and the battery is charging. In case of
a mains power supply failure the luminaire will
light the led strip automatically in emergency
mode (powered by its battery). When the
mains power supply is restored the device
turns to normal operation.
OPERATION
Battery Charging
The battery charging is completely controlled.
In this case, the best possible
maintenance is achieved, as well as the
elongation of its duration. When the battery
has completely charged, it charges with a
maintenance current.
Battery Cut-off
The luminaire enters in this operation when
the mains power supply fails and battery has
lost its energy. During this operation the
luminaire enters the idle state and battery
consumption is negligible, in order to be
protected from deep discharge.
Page 1 from 5
WATERPROOF SELF TESTING MAINTAINED
GR-577/L/15/ST/WP
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
7480gr (double side)
Thank you for your trust in our products.
Olympia Electronics - European manufacturer.
battery
(for LED MODULE Specs. see page 5)
220-240V AC/50-60Hz
9W / 9.5VA - PF: 0.95/230V
4.8V/1.5Ah
From overcharge and deep discharge
Charge LED, Lamp Fault, Battery Fault
24 h
90 min
White LEDs
680lm / 340lm
IP 66
5 to 40 C
Up to 95%
Painted steel plate (RAL 7036), ABS/PC, PC
480 x 480 x 105 mm
3 years (1 year for the battery)
Manual Test
This test can be done by placing the test card
on the side of the indications (page 4)
remove it instantly an operation test is initiated.
The light source and the emergency circuit of
the device is monitored. The manual test can
be conducted only if the mains power supply
and the battery is connected. During this test
period all indication LEDs are OFF.
Automatic Operational Test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the
mains power supply and the battery should be
connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the device's back up operation
and emergency duration. This test is conducted
automatically every 6 months. In order to be
performed, the mains power supply and the
battery should be connected and fully charged.
If the battery is not fully charged, the test is
postponed until the battery is completely
charged. If during this test, the autonomy is less
than nominal then the battery fault led turned
on continuously and the battery must be
replaced.
GR-577/L/15/ST/WP/O
o
7630gr
923577007_09_001
and

Advertisement

loading

Summary of Contents for olympia electronics GR-577/L/15/ST/WP

  • Page 1 7630gr 3 years (1 year for the battery) GUARANTEE Thank you for your trust in our products. Olympia Electronics - European manufacturer. GENERAL Manual Test These luminaires are used in places where This test can be done by placing the test card emergency luminaires are needed.
  • Page 2: Installation

    Back Up Operation ΑΤΤΕΝΤΙΟΝ!!! The autonomous duration of battery during 1. Operations for installation, maintainance emergency mode is at least the one that is or testing must be done by authorized stated list technical personnel only, after a mains interruption. characteristics.
  • Page 3: Installation Instructions

    INSTALLATION INSTRUCTIONS 1. Remove the front cover by unscrewing the retaining screws. Remove the acrylic plate. 2. Always use in any case round mains cable, with a diameter of 12-14mm (H05RN-F type 4x1mm² or any other type, at least equal to it’s mechanical and electrical properties). ATTENTION!! The cable must not be deformed in any way (This requirement is important to ensure the tightness isolation IP 66).
  • Page 4 MOUNTING The luminaires of this series can be mounted in parallel to the wall of the tunnel (single sided) for indicating exit routes or vertically to the wall for indicating the position of exit routes or the position of emergency phones There is also, after request, capability for installation to the wall with an angle.
  • Page 5: Led Indications

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Gr-577/l/15/st/wp/o