ADDRESSABLE SELF TESTING MAINTAINED EMERGENCY LUMINAIRES WITH WHITE LEDs
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
BATTERY PROTECTION
INDICATIONS
- CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
ILLUMINATION (230V AC / emergency)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used indoors (ta 40 C)
where emergency light is needed. Each
luminaire must be permanently connected to
mains power supply. In normal operation (L1
connected to L) the led strip lights and the
battery is charging. In case of a mains power
supply failure the luminaire will light the led
strip automatically in emergency mode
(powered by its battery). When the mains
power supply is restored the device turns to
normal operation.
Address Operation
The luminaires can be connected to a GR-
6500 address panel. For address operations
refer to the installation manual of the panel.
For address module connections see page 4.
For dip-switch addressing selection see
pages 6 and 7.
Battery Charging
The battery charging is completely controlled.
In this case, the best possible
maintenance is achieved, as well as the
elongation of its duration. When the battery
has completely charged, it charges with a
maintenance current.
Page 1 from 7
GR-1315/15L/ADR
3.4W/3.8VA
3.6V/0.6Ah
Charge, Lamp Fault, Battery Fault indication LED, TEST Button
15 white LEDs
105lm / 105lm
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
670gr.
Thank you for your trust in our products.
Olympia Electronics - European manufacturer.
battery
(for LED MODULE Specs. see page 5)
GR-1315/30L/ADR
220-240V AC/50-60Hz
4.5W/4.9VA
3.6V/1.5Ah
From overcharge and deep discharge
90min
30 white LEDs
210lm / 210lm
5 to 40 C
Up to 95%
Bayblend FR3010, transparent polycarbonate
353 x 143 x 57 mm
3 years (1 year for the battery)
Battery Cut-off
o
The luminaire enters in this operation when
the mains power supply fails and battery has
lost its energy. During this operation the
luminaire enters the idle state and battery
consumption is negligible, in order to be
protected from deep discharge.
Manual Test
The manual test can be conducted only if the
main power supply and the battery is
connected. By pressing the test button briefly
an operation test is initiated. During this test
period all indication LEDs are OFF.
Tests
Normally the illumination source and the
autonomy tests are programmed by the
control panel and the test results are sent to
the control panel.
If the luminaire is not connected to GR-
6500 panel, the following automatic tests
executed:
Automatic Operational Test
This test includes all the operations that
provide the manual test and is conducted
automatically every 15 days. In order to be
performed, the mains power supply and the
GR-1316/15L/ADR
GR-1316/30L/ADR
3.3W/3.7VA
24h
180min
15 white LEDs
30 white LEDs
105lm / 105lm
IP 40
o
750gr.
923131605_09_003
5.3W/5.6VA
3.6V/3Ah
210lm / 210lm
820gr.