olympia electronics GR-292/M/HL/ADR Installation Instructions Manual

Addressable self testing non-maintained emergency ceiling mounted luminaires

Advertisement

Quick Links

ADDRESSABLE SELF TESTING NON-MAINTAINED EMERGENCY CEILING MOUNTED LUMINAIRES
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAX. SUPPLY CURRENT
MAXIMUM POWER CONSUMPTION
MINIMUM POWER FACTOR (λ)
U-OUT
BATTERY
INSULATION BETWEEN SUPPLY & CONTROL TERMINALS
INSULATION BETWEEN SUPPLY & BATTERY CIRCUIT
WORKING VOLTAGE AT WHICH THE INSULATION IS DESIGNED
BATTERY PROTECTION
BATTERY VOLTAGE RANGE
BATTERY SUPPLY CURRENT DURING EMERGENCY
BATTERY CHARGE CURRENT RANGE
BATTERY DISCHARGE CURRENT RANGE
INDICATIONS - CONTROLS
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE
EMERGENCY ILLUMINATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
Prated/Irated
CONTROL GEAR MAX.TEMPERATURE (tc)
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION
WEIGHT
GUARANTEE
CONTROL GEAR WITH AUTOMATIC
TEST FUNCTION
Do NOT stare at operating light source.The luminaire should be positioned so that
prolonged staring into the luminaire at a distance closer than 0.4m is not expected.
E = 718 lux.
thr
GENERAL
This device is used indoors (ta 40 C) in places
where emergency luminaires are needed. Each
device must be permanently connected to mains
power supply. The GR-292/M/HL/ADR is
suitable for corridors lighting and the GR-
293/M/HL/ADR for open area lighting. In normal
operation the battery is charging. In case of a
mains power supply failure, the device enters
emergency mode and the illumination LED turns
on. When the mains power supply is restored,
the device turns to normal operation.
Page 1 from 8
GR-292/M/HL/ADR
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Controlgear is suitable for LED module only
The controlgear has mains-connected windings of transformer
Thank you for your trust in our products
Olympia Electronics - European manufacturer
o
(for LED MODULE specifications see page 8)
220-240V AC / 50-60Hz
19.5mA AC
4.9W / 5.2 VA
4.8V/4Ah, NiMH (4KRMT 23/62)
Basic insulation
Basic insulation
Deep discharge and overcharge protection
(Vbat=4.8V):650mA
130 - 200mA (normal charge) / 20 - 30mA (trickle charge)
550 - 730mA
Charge, lamp fault, battery fault, TEST button
24 hours
3 hours
1 white power LED
5 to 40 C
2.3W/760mA
80°C at Q2
Up to 95%
ABS/PC
Ø125 x 72 mm
3 years (1 year for the battery)
Battery Charging
The battery charging is completely controlled. In
this case, is achieved the perfect
maintenance , as well as the elongation of its
duration. When the battery has completely
charged, it charges with a maintenance current.
Battery charge failure due to shortcut
The recharging device will recharge the battery
normally after the short circuit is removed and the
batterie(s) are reinstalled.
Battery Cut-off
The device enters this mode when the mains
power supply has failed and battery has lost its
GR-293/M/HL/ADR
0.9
6V
500V
4-6V
330lm
IP20
o
737gr.
923293008_09_002
battery

Advertisement

loading

Summary of Contents for olympia electronics GR-292/M/HL/ADR

  • Page 1 , as well as the elongation of its power supply. The GR-292/M/HL/ADR is duration. When the battery has completely suitable for corridors lighting and the GR- charged, it charges with a maintenance current.
  • Page 2: Status Of Leds

    energy. During this mode the device enters in idle errors). state and battery consumption is negligible, in ΑΤΤΕΝΤΙΟΝ!!! order to be protected from deep discharge. 1. Operations for installation or maintainance Manual Test must be done by authorized personnel only. This test can be done by pushing the test button.
  • Page 3: Installation Instructions

    INSTALLATION INSTRUCTIONS Communication Connection Cable Power Connection entry hole Battery Connection 2 3 4 5 6 7 8 Dipswitch Position BEWARE of electric shock after reflector removal. Plastic base could contain live parts if connected to mains supply. Initial installation 1 Untighten the screw and pull up the reflector.
  • Page 4 Mounting the lamp in suspended ceiling. Set up the lamp to the suspended ceiling as it is shown bellow (Required opening 110mm): Step 1 Pass the battery pack into the ceiling then bend the springs, to get into the hole of the suspended ceiling, as you can see to the next figure.
  • Page 5 Dipswitch Dipswitch Dipswitch Dipswitch Address Address Address Address setting setting setting setting Page 5 from 8 923293008_09_002...
  • Page 6 Dipswitch Dipswitch Dipswitch Dipswitch Address Address Address Address setting setting setting setting Page 6 from 8 923293008_09_002...
  • Page 7 Dipswitch Address setting GR-292/M/HL/ADR (Escape Route) 72 mm 50 mm Corridor 125 mm lighting LAMP BATT. CHARGE TEST 96 mm FAULT LAMP BATT. CHARGE TEST FAULT Lamp fault ATTENTION!!! indication LED During installation follow this light direction. GR-293/M/HL/ADR Battery Battery...
  • Page 8: Warranty

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Gr-293/m/hl/adr