5.9

Electrodes adjustment

Position the electrodes according to the dimen-
sions shown in Fig. 18.
WARNING
5.10

Combustion head adjustment

The air damper servomotor 4)(Fig. 4), beyond varying the air out-
put according to the output demand, through a leverage varies
the combustion head adjustment.
This system allows an optimum adjustment also at the minimum
firing rate. Similarly to servomotor rotation, it is possible to vary
the opening of the combustion head moving the tie-rod on the
holes (5-6-7-8-10)(Fig. 19).
20061124
20123781
Installation
D11587
The selection of the hole to be used is determined based on the
maximum output requested, as illustrated in Tab. I.
In the factory, the adjustment is adjusted for the maximum stroke
(hole 10, Fig. 19).
Leverage hole
5
5
8
10
5
5
6
10
The gas pipes leave the factory calibrated at
notch 1.
Fig. 19
The adjustment shown in Fig. 20 allows the gas
WARNING
pipes to be positioned in the best way for the ap-
plication on which the burner is installed (e.g. boil-
ers with flame inversion chamber).
20
GB
Electrodes
Diffuser
Output (kW)
From
1100
4000
6600
8100
1500
5500
7500
9650
20077710
Fig. 18
A
4000
6600
8100
10100
5500
7500
9650
11100
Tab. I
Fig. 20