Technical data

Model
Type
Power
(1)
Output
(1)
Fuels
Gas pressure at max. output
Gas: G20/G25
Operation
Standard applications
Ambient temperature
Combustion air temperature
Noise levels
Sound pressure
(3)
Sound power
Weight
Reference conditions: ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(1)
Pressure on the socket 5) (Fig. 4) with zero pressure in the combustion chamber and at maximum burner output.
(2)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output. The sound
(3)
power is measured with the "Free Field" method, as per EN 15036, and according to an "Accuracy: Category 3" measuring accuracy, as set out in
EN ISO 3746.
4.4

Electrical data

Model
Electrical supply
Fan motor IE3
Ignition transformer
Absorbed electrical power
Protection level
20123781
Technical description of the burner
min - max
kW
Natural gas: G20 (methane gas) - G21 - G22 - G23 - G25
-
(2)
mbar
-
-
-
°C
°C max
dB(A)
Kg
rpm
Hz
V
kW
A
V1 - V2
I1 - I2
kW max
RS 1000/EV BLU
1133 T2
1100/4000 - 10100
64.5/92.7
Intermittent (min. 1 stop in 24 hours)
Continuous (min. 1 stop in 72 hours)
Modulating
Boilers: water, steam, diathermic oil
85
99
460
RS 1000/EV BLU
3N ~ 400V +/-10% 50 Hz
2880
50
400/690
22
38,2/22,3
230 V - 2 x 5 kV
1.9 A - 35 mA
24
8
GB
RS 1200/EV BLU
1134 T2
1500/5500 - 11100
80.5/114
0 - 50
60
89.3
99.7
500
RS 1200/EV BLU
2880
50
400/690
25
43,4/25,1
27.2
IP 55
Tab. B
Tab. C