Step 14 — Adjust Factory- -Installed Options
Smoke Detectors —
Smoke detector(s) will be connected at the Controls
Connections Board,
at
Shutdown". Cut jumper JMP 3 when ready to energize
unit.
EconoMi$er IV Occupancy Switch —
Refer to Fig. 61 for general EconoMi$er IV wiring.
External occupancy control is managed through a
connection on the Controls Connections Board.
If external occupancy control is desired, connect a time
clock or remotely controlled switch (closed for Occupied,
open for Unoccupied sequence) at terminals marked
OCCUPANCY. Cut jumper JMP 2 to complete the
installation.
Step 15 — Install Accessories
Available accessories include:
Curb
Thru- - base connection kit (must be installed before unit
is set on curb)
LP conversion kit
Flue discharge deflector
Fig. 61 - - EconoMi$er
terminals
marked "Smoke
R
IV Wiring
Manual outside air damper
Two- - Position motorized outside air damper
EconoMi$er X (with control)
EconoMi$er IV (with control)
EconoMi$er2 (without control/for external signal)
Power Exhaust
Differential dry- - bulb sensor (EconoMi$er IV)
Outdoor enthalpy sensor
Differential enthalpy sensor
CO
sensor
2
Louvered hail guard
Motormaster head pressure controls
Phase monitor control
Refer to separate installation instructions for information
on installing these accessories.
Pre- - Start and Start- - Up
This completes the mechanical installation of the unit.
Refer to the unit's Service Manual for detailed Pre- - Start
and Start- - Up instructions. Download the latest versions
from HVAC Partners (www.hvacpartners.com).