Outdoor Air Enthalpy Control; Differential Enthalpy Control - Bryant 582J Series Installation Instructions Manual

Single package rooftop gas heating/electric cooling unit sizes 04-06 with puronr r-410a refrigerant
Hide thumbs Also See for 582J Series:
Table of Contents

Advertisement

If this LED is on...
Power
Rx
Tx
BO#
The Run and Error LEDs indicate control module and network status
If Run LED shows...
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per second
5 flashes per second
5 flashes per second
7 flashes per second
14 flashes per second
On
NOTE: Refer to the RTU Open multi- - protocol controller
Controls, Start- - Up, Operation and Troubleshooting manual
for complete configuration of RTU Open, operating
sequences and troubleshooting information. Contact your
Bryant applications engineer for details on configuration
and troubleshooting of connected networks.

Outdoor Air Enthalpy Control

(PNO 33CSENTHSW)
The enthalpy control (33CSENTHSW) is available as a
field- - installed accessory to be used with the EconoMi$er
damper system. The outdoor air enthalpy sensor is part of
the enthalpy control. (The separate field- - installed accessory
return air enthalpy sensor (33CSENTSEN) is required for
differential enthalpy control. See Fig. 57.)
Locate the enthalpy control in the economizer next to the
Actuator Motor. Locate two GRA leads in the factory
harness and connect the gray lead labeled "ESL" to the
terminal labeled "LOW". See Fig. 57. Connect the enthalpy
control power input terminals to economizer actuator power
leads RED (connect to 24V) and BLK (connect to GND).
Table 7 – LEDs
The LEDs on the RTU Open show the status of certain functions
Status is...
The RTU Open has power
The RTU Open is receiving data from the network segment
The RTU Open is transmitting data over the network segment
The binary output is active
And Error LED shows...
Off
2 flashes, alternating with Run LED
3 flashes, then off
4 flashes, then pause
On
On
Off
7 flashes per second, alternating with
Run LED
14 flashes per second,
alternating with Run LED
On
R
Status is...
Normal
Five minute auto---restart delay after system error
Control module has just been formatted
Two or more devices on this network have the
same MSTP network address
Exec halted after frequent system errors or
control programs halted
Exec start---up aborted, Boot is running
Firmware transfer in progress, Boot is running
Ten second recovery period after brownout
Brownout
Failure. Try the following solutions:
S Turn the RTU Open off, then on.
S Format the RTU Open.
S Download memory to the RTU Open.
S Replace the RTU Open.
Enthalpy
Switch
24V
GND
LOW
Fig. 57 - - Enthalpy Switch (33CSENTHSW) Connections
2
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
Differential Enthalpy Control —
Differential enthalpy control is provided by sensing and
comparing the outside air and return air enthalpy
conditions. Install the outdoor air enthalpy control as
described above. Add and install a return air enthalpy
sensor.
36
RED
PL6-1 (24-V)
BLK
PL6-4 (COM)
GRA
7
CTB ECON
(P'LINK: to J4-2) or
(RTU Open: to J2-6)
Factory Wiring Harness
C11160