Assembly, commissioning and maintenance of the fans Measurement, analysis and evaluation of all the data required for operation (e.g.: pressure, volume, sound, vibrations) Operational balancing Replacement parts service Individual advice and help placing orders Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
The system owner must have all safeguards tested regularly to ensure that they are functional and com- The age-specific and occupational regulations appli- plete. cable at the operation site must be observed when appointing personnel. Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
The danger increases from explosion group IIA to IIC. (The higher explosion group includes the lower ones.) – Only use the unit for its correct use. – Strictly comply with all of the information in this operating manual. Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
The source of the vibration can be decoupled from the surrounding area using a vibration damper. – Do not deactivate the vibration damper. – Do not remain in the vibrating area during opera- tion. Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
Before the unit is unit started up, install emergency stop equipment for the unit and connect it to the system con- trol’s safety chain. This does not apply to smoke exhaust fans. Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
Page 15
Safety Labelling Fig. 4: Terminal box The (Fig. 4/1) “Danger of death due to electric current” symbol is attached to the terminal box. Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
3.3 Connection values The connection values are dependent on the type of electric motor that is installed (electric motor’s rating Ä 3.1 ‘Design versions’ on page 16). plate, see Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
The fire safety engineering occur, as long as the penetration of precipitation in the requirements must be observed. vicinity of the intake and outlet openings is prevented with suitable measures. Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
/ time category. In addition, a CE mark as per EN 12103, Part 3, is attached to demonstrate product conformity. Fig. 14: Arrangement of the rating plates on axial fans Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
Page 21
Category Fig. 15: Electric motor’s rating plate The electric motor’s rating plate (Fig. 15, Fig. 14/2) is located on the outside. For information on this rating plate, refer to the electric motor operating manual. Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
No operations are executed on the axial fan. 4.3 Description of the sub-assembly 4.3.1 Casing The casing for axial fans comprises a duct casing and a motor block. The casing can optionally comprise outlet guide vanes and a motor mount. Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
Page 27
Fig. 30: Axial fan with acoustic and thermal insulation Easy-to-install shell structure for acoustic and thermal insulation. Vibration isolators Reduction of the transmission of vibrations from the fan to the installation location (depending on the weight as a spring or rubber vibration isolator). Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
Change the frequency inverter’s parameter set- tings The duct system’s pres- What operating point is the fan working in? Instructed person sure losses are higher Change the duct version; prevent turbulances than expected / calcu- using baffle plates. lated Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
Page 40
Clean the casing / impeller Instructed person casing or impeller Impeller is grinding Caused by a misaligned connection duct due to Instructed person deformation of the casing, for example. Check the impeller gap Realign the fan Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
Reset the emergency stop equipment. Acknowledge the fault on the control. Ensure that nobody is in the hazardous area. Start in accordance with the information in the Ä 7 ‘Operation’ on page 36”. chapter entitled “ Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
Number: min. 5 Use reverse dampers in the intake duct. Install a flexible connector to further improve the inflow. Size flexible con- nectors so that they are two nominal sizes bigger than the fan’s nominal size. Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
above and around the axial fan. Fig. 42: Minimum distance The minimum distance between the axial fan and the walls and neighbouring axial fans must be at least 0.5 x the fan size. Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
Fan is free of foreign matter (tools, dirt, etc.). ☐ Impeller rotates freely. ☐ Impeller gap corresponds to information provided in Chapters 12.3.4 and 12.3.5 ☐ Screw connections are secure (see screw tightening torques in Chapter 12.3.1). Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
If the current is measured using the current probe on the fan terminal box and star / delta circuit, the measured value must be multiplied by Ö3 and logged. If the nominal current is exceeded, the cause must be determined and eliminated according to . Notes Maintenance carried out by: Date Signature Executor System owner Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
Page 58
The bearings’ service life is generally 20,000 h, but the actual service life can deviate considerably from this depending on the bearing load. The operating instructions provided by the motor manufacturer are available for download from the manufacturer’s website. Recommendation: An annual bearing check should be performed. Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
Page 59
The bearings’ service life is generally 20,000 h, but the actual service life can deviate considerably from this depending on the bearing load. The operating instructions provided by the motor manufacturer are available for download from the manufacturer’s website. Recommendation: An annual bearing check should be performed. Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...
Guide the connecting cables outside. Assemble the extension ducts. Disconnect the terminal boxes from the console. Screw on the console extension sheets. Assemble and wire the terminal boxes and diagnostic units. Perform a motor functional test. Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN...