Siemens SINAMICS S120 Manual page 90

Power units in booksize c/d-type format
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor connection, shield support and fabrication
4.2 Motor connection block for 45 A / 60 A Motor Modules
Figure 4-5
Table 4- 5
Maximum dimensions
Figure 4-6
Note
Cable lugs for 50 mm
For cables with a cross-section of 50 mm
with additional shrink-on sleeve to maintain touch protection. Other tubular cable lugs cannot
be used because the maximum possible cable lug width is 18.5 mm.
88
Dimension drawing of the motor connection block
Dimensions of the motor connection block in mm (inch)
a
42 (1.65)
Fillets at the motor connection block that can be removed to connect cables from a diameter of
9.5 mm (0.37 in) and higher. The fillets have already been removed on the right-hand side.
Fan unit for 45 A / 60 A Motor Modules
cables
2
b
c
24.5 (0.96)
12 (0.47)
, use tubular cable lugs from Klauke, article 6SG6,
2
d
e
18.5 (0.73)
15.6 (0.61)
Power Units in Booksize C/D-Type Format
Manual, 12/2018, 6SL3097-5AC20-0BP0
f
10.5 (0.41)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents