5.1.3

Technical data

Table 5- 2
Technical data, motor reactors, part 1
Article No.
Suitable for Motor Modules
booksize C/D type
Rated current
Maximum current
Inductance
Power loss
Motor cable connection
Protective conductor connection
Maximum motor cable lengths
shielded: 1 / 2 reactors
unshielded: 1 / 2 reactors
Degree of protection according to
EN 60529
Ventilation clearances
above/below
Weight
Power Units in Booksize C/D-Type Format
Manual, 12/2018, 6SL3097-5AC20-0BP0
6SE7021-
0ES87-1FE0
6SL3120-
1TE13-0AD.
2TE13-0AD.
1TE15-0AD.
2TE15-0AD.
A
5
A
10
μH
1243
W
80
Screw-type terminals
4 mm
2
m
100 / -
m
150 / -
mm
kg
5.5
Motor-side power components
6SL3000-
6SE7022-
2BE21-0AA0
6ES87-1FE0
6SL3120-
6SL3120-
1TE21-0AD.
2TE21-0AD.
9
18
1000
90
Screw-type terminals
16 mm
2
Threaded bolts M6
135 / -
200 / -
IP00
≥ 100
4.8
5.1 Motor reactors
1TE21-8AC.
1TE21-8AD.
2TE21-8AC.
2TE21-8AD.
18
36
332
110
Screw-type terminals
16 mm
2
160 / 320
240 / 480
7.8
95