Siemens SINAMICS S120 Manual page 80

Power units in booksize c/d-type format
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor connection, shield support and fabrication
4.1 Motor plug connector for Motor Modules 3 A ... 30 A
Figure 4-2
Table 4- 3
Conductor and stripped insulation lengths as a function of the cable cross-section, data in mm and (inch)
U
(2.17 +0.08/-0.12)
V
W
Protective
conductor
(2.52 +0.08/-0.12)
BR-
(2.87 ±0.20)
BR+
(3.11 ±0.20)
Note
Adherence to conductor and stripped insulation lengths
If the specified conductor and insulation stripping lengths are not complied with, individual
conductors can be damaged or shield contact prevented.
78
Conductors U-V-W
Protective conductor core
Holding brake conductors
Protective braided shield
Shrink tubing
Conductor and stripped insulation lengths
1.5 mm
(AWG 16)
2
a
55 +2/-3
12 ±0.5
(0.47 ±0.02)
64 +2/-3
12 ±0.5
(0.47 ±0.02)
73 ±5
12 ±0.5
(0.47 ±0.02)
79 ±5
12 ±0.5
(0.47 ±0.02)
2.5 / 4 / 6 mm
b
55 +2/-3
(2.17 +0.08/-0.12)
62 +2/-3
(2.44 +0.08/-0.12)
73 ±5
(2.87 ±0.20)
79 ±5
(3.11 ±0.20)
(AWG 14 / AWG 12 / AWG 10)
2
a
(0.47 ±0.02)
(0.47 ±0.02)
(0.47 ±0.02)
(0.47 ±0.02)
Power Units in Booksize C/D-Type Format
Manual, 12/2018, 6SL3097-5AC20-0BP0
b
12 ±0.5
12 ±0.5
12 ±0.5
12 ±0.5