Siemens SIMOTICS XP 1MB155 Operating Instructions Manual page 75

Low-voltage motors
Table of Contents

Advertisement

Frame size Enclosure grounding method
132 ... 355 Cable connection with free cable
The additional threaded hole on the grounding socket is optionally available for additional
equipotential bonding of high-frequency voltages and currents in converter operation.
Internal ground terminal
When making connections, ensure the following:
● Ensure that the connecting surface is bare and is protected against corrosion using a
suitable substance, e.g. acid-free Vaseline.
● Arrange the flat washer and spring washer under the bolt head.
● Locate the cable lug under the clamping bracket.
● Use the terminals designated for the grounding conductor in the terminal box.
● Observe the tightening torque for the locking screw.
External ground terminal
When making connections, ensure the following:
● Ensure that the connecting surface is bare and is protected against corrosion using a
suitable substance, e.g. acid-free Vaseline.
● Position the cable lug between the contact bracket and the grounding bracket; do not
remove the contact bracket pressed into the enclosure!
● Arrange the flat washer and spring washer under the bolt head.
1MB155 / 1MB555
Operating Instructions, 03/2018, A5E41926185A
Cable connection with grounding strap
Cable connection with cable lug
(DIN 46234; JB/T2436.1)
Electrical connection
6.4 Connecting the grounding conductor
73

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotics xp 1mb555

Table of Contents