This version of the Installation Manual, which you may occur between structures and the building can do by contacting Clenergy Australia via and also between structures, fasteners and PV email on sales@clenergy.com.au, or contacting modules, as detailed in AS/NZS 5033: 2014.
Local authorities will advise if this applies in your area. ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 4
Terrain Category 4 (TC4) – Terrain with numerous larger, high (10m to 30m tall) and closely-spaced buildings, such as large city centers and well-developed industrial complexes. If your installation site is not at TC 2, 2.5 or 3, please contact Clenergy to obtain a project specific engineering certificate to support your installation.
Page 5
Certification Letter and Tilt Legs Spacing Table. ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 6
Step 5: The lowest value in step 4, equates to a. ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 7
2. Rear leg adjustable range: ER-TL-10/15: 260-375 mm; ER-TL-15/30: 390-635 mm; ER-TL-30/60: 675-1205 3. If the info. is different from the table and diagram, it could have different results. Please contact the Clenergy to confirm its applicability. ® Installation Guide-PV-ezRack...
Page 8
Planning ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 9
Planning ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 10
Planning ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 11
Planning (10) ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 12
Planning (11) (12) ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 13
Planning (13) (14) ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 14
Planning (15) ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
⑤ Grounding Lug ⑥ Adjustable Tilt Legs with L-feet ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 17
(grease or 40# engine oil) to fasteners prior to tightening. ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 18
Please refer to safe torques defined in this guide as shown in the figure below. If power tools are required, Clenergy recommends the use of low speed only. High speed and impact drivers increase the risk of bolt galling (deadlock). If deadlock occurs and you need to cut fasteners, please make sure that there is no load on the fastener before you cut it.
Page 19
® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 24
(e.g. ASE250) M8 x 20 mm bolts must be used. Figure 18 ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 25
Figure 23 ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 26
Figure 26 Figure 27 ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 27
The recommend torque for Universal Clamps in the Inter Clamp position is 16~20N·m. ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 28
Figure 33 ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Certification Letter and Tilt Legs Spacing Table ® Installation Guide-PV-ezRack SolarRoof Tilt Leg (September 2020) page of 28 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 30
20 August 2020 Clenergy Australia 1/10 Duerdin Street Clayton, VIC 3168 CERTIFICATION LETTER Clenergy PV ez‐Rack SolarRoof penetrative tilt interface certification – TC2, 2.5, 3 – Wind Region A, B, C and D. Internal REF: 00400. MW Engineering Melbourne, being Structural Engineers within the meaning of Australian regulations, have calculated the maximum spacings for the PV ez‐Rack rail system for the following conditions: ‐ Wind Loads to AS 1170.2‐2011 AMDT 4‐2016 o Wind Terrain Category 2, 2.5 and 3 o Wind average recurrence of 200 years o Wind Region A, B, C and D ‐ Solar panel length up to 2.2 m ...
Page 31
MW Engineering Melbourne constitutes an infringement in copyright. Limitation: This report has been prepared for the exclusive use of Clenergy Australia and is subject to and issued in connection with the provisions of the agreement between MW Engineering Melbourne and Clenergy Australia.
Page 34
PV ez-Rack SolarRoof Interface spacing table for penetrative tilt legs Type of Rail ER-R-ECO (see Note 12 for other compatible rails) Solar Panel Dimension 2 m x 1 m (see Note 23 for other panel sizes) Terrain Category Angle against horizontal < 10° Building Height (m) H <...
Page 35
PV ez-Rack SolarRoof Interface spacing table for penetrative tilt legs (Cont.) Type of Rail ER-R-ECO (see Note 12 for other compatible rails) Solar Panel Dimension 2 m x 1 m (see Note 23 for other panel sizes) Terrain Category Angle against horizontal - 20° < α < 25° Building Height (m) H <...
Page 36
PV ez-Rack SolarRoof Interface spacing table for penetrative tilt legs (Cont.) Type of Rail ER-R-ECO (see Note 12 for other compatible rails) Solar Panel Dimension 2 m x 1 m (see Note 23 for other panel sizes) Terrain Category Angle against horizontal - 30° < α < 60° Building Height (m) H <...
Page 37
PV ez-Rack SolarRoof Interface spacing table for penetrative tilt legs Type of Rail ER-R-ECO (see Note 12 for other compatible rails) Solar Panel Dimension 2 m x 1 m (see Note 23 for other panel sizes) Terrain Category Angle against horizontal < 10° Building Height (m) H <...
Page 38
PV ez-Rack SolarRoof Interface spacing table for penetrative tilt legs (Cont.) Type of Rail ER-R-ECO (see Note 12 for other compatible rails) Solar Panel Dimension 2 m x 1 m (see Note 23 for other panel sizes) Terrain Category Angle against horizontal - 20° < α < 25° Building Height (m) H <...
Page 39
PV ez-Rack SolarRoof Interface spacing table for penetrative tilt legs (Cont.) Type of Rail ER-R-ECO (see Note 12 for other compatible rails) Solar Panel Dimension 2 m x 1 m (see Note 23 for other panel sizes) Terrain Category Angle against horizontal - 30° < α < 60° Building Height (m) H <...
Page 40
PV ez-Rack SolarRoof Interface spacing table for penetrative tilt legs Type of Rail ER-R-ECO (see Note 12 for other compatible rails) Solar Panel Dimension 2 m x 1 m (see Note 23 for other panel sizes) Terrain Category Angle against horizontal < 10° Building Height (m) H <...
Page 41
PV ez-Rack SolarRoof Interface spacing table for penetrative tilt legs (Cont.) Type of Rail ER-R-ECO (see Note 12 for other compatible rails) Solar Panel Dimension 2 m x 1 m (see Note 23 for other panel sizes) Terrain Category Angle against horizontal - 20° < α < 25° Building Height (m) H <...
Page 42
PV ez-Rack SolarRoof Interface spacing table for penetrative tilt legs (Cont.) Type of Rail ER-R-ECO (see Note 12 for other compatible rails) Solar Panel Dimension 2 m x 1 m (see Note 23 for other panel sizes) Terrain Category Angle against horizontal - 30° < α < 60° Building Height (m) H <...
Page 43
Note 1. This engineering document was designed to cater for most common installation scenarios however, it does not cater for all of them. Contact Clenergy if you are unable to comply with any of the installation specifications listed on this document.
Page 44
Note 11. In case the installation is done with one screw and the purlin thickness differs from Note 6, a site-specific certificate shall be issued. Contact Clenergy for more information. Note 12. The following components are satisfied for use according to AS/NZS 1664.1:1997-Amdt 1:1999 and AS/NZS 1170.2:2011 Amdt 4-2016.
Page 45
Components Part No. Description End Clamp = Clamp + Z- End Security Clamp ER-EC-STXX/S Module + Security Bolt 10°/15° Adjustable Tilt Tilt Legs ER-TL-10/15 Legs 15°/30° Adjustable Tilt Tilt Legs ER-TL-15/30 Legs 30°/60° Adjustable Tilt Tilt Legs ER-TL-30/60 Legs 10°/15° Adjustable Tilt Tilt Legs ER-TL-10/15/PS Legs, Preassembly...
Page 46
(R2016) for more information. Note 17. The installed frame must comply with the clamping zone of the PV Panel. Note 18. Capacities checked and compared against testing data from Clenergy Australia and NATA certified testing. Note 19. Maximum permitted rail overhang of 40% of the installation spacing.
Page 47
Note 21. All components from Clenergy must be installed according to manufacturer's specification and the instructions shown in the relevant installation manual. Please check the Clenergy Australia website or contact them for access to the most recent installation manuals. Note 22. No consideration has been taken on the effect of snow loads. In case the roof is located in a snow prone area, a project specific design must be completed.
Page 48
Reverse tilt Back leg angle between 30° and 90° ECO – Rail parallel to ribs Back leg angle between 30° and 90° Note 26. If any of the screws of the interfaces go into pre-existing holes, they will have to be one size up compared to the screws that were previously installed.
Page 49
Note 27. Roof Zone definition to be calculated as per below: Step 1. Determine building height (h), width (b) and length (d). Step 2. Choose the lowest value between "h", "b x 0.2" and "d x 0.2". Step 3. The lowest value on Step 2, equates to a. Roof Pitch <...