Table 4-4 One-Way Wire Distance and Wire Size for a 24 Vdc System
Maximum one-way wire distance for a < 3% voltage drop assuming 60 Adc charging current
Distance in feet (meters)
Amps
12 AWG
10
17.6 (5.36)
28.0 (8.54)
12
14.6 (4.46)
23.2 (7.08)
14
12.6 (3.84)
20.0 (6.10)
16
11.0 (3.36)
17.4 (5.30)
18
9.8 (2.98)
17.6 (4.76)
20
8.8 (2.68)
14.0 (4.26)
25
11.2 (3.42)
30
9.4 (2.86)
35
40
45
50
60
a.These wire sizes are not approved by UL to be installed in the controller, but may be used external to the controller (using a splicer block) to reduce
voltage drop and improve performance.
Table 4-5 One-Way Wire Distance and Wire Size for a 48 Vdc System
Maximum one-way wire distance for a < 3% voltage drop assuming 60 Adc charging current
Distance in feet (meters)
Amps
12 AWG
10
70.4 (21.44)
112.0 (34.16)
12
58.4 (17.84)
92.8 (28.32)
14
50.4 (15.36)
80.0 (24.40)
16
44.0 (13.44)
69.6 (21.20)
18
39.2 (11.92)
70.4 (19.04)
20
35.2 (10.72)
56.0 (17.04)
25
44.8 (13.68)
30
37.6 (11.44)
35
40
45
50
60
a.These wire sizes are not approved by UL to be installed in the controller, but may be used external to the controller (using a splicer block) to reduce