Configuration from Ladder Editor
3.2.3
The EH-150 CPU has two link areas of 1024 words (No.1 LINK and No.2 LINK).
The EH-RMP operates in the EH-150 system as a LINK module. The first EH-RMP in a rack uses No.1 LINK area
and the second EH-RMP uses No.2 LINK area .
For the EH-RMP, specify the output area size of the link ( maximum 256 words).
Top Assign No. is fixed to WL0. (for No.2 LINK is WL1000.)
Last Assign No. is between WL0 and WLFF. (for No.2 LINK is between WL1000 and WL10FF.)
Input area of the link is always fixed from WL200 to WL2FF ( for No.2 LINK is WL1200-WL12FF).
Fig. 3.7 LINK Parameter
NOTE1:
All address in the link area are word addresses.
All address in the configurator(SyCON DP) are byte addresses.
NOTE2:
The EH-150 CPU uses 1024 words for the EH-RMP.
But the effective data area is 256 words of input data and 256 words of output data.
512 words of the remainder are reserved.
WL0
Output area
RESERVED
WL200
Input area
WL300
RESERVED
WL3FF
Fig. 3.8 LINK area 1 mapping
Chapter 3 CONFIGURATIONS
Depending on the above link parameter
3-7