Specification - Hitachi HIDIC EH-150 Applications Manual

Profibus-dp master module
Hide thumbs Also See for HIDIC EH-150:
Table of Contents

Advertisement

2.2 Specification

ITEM
Power source
General
Operating ambient temperature
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Noise resistance
Dielectric withstand voltage
Consumption current
Usage environment
Structure
Cooling
Function
Number of modules
Number of slaves
Output data
Input data
I/O assignment
Data transfer rate :
Self-diagnosis
GSD file
Configurator
1) LINK area(1024 word ) is used. Can not use for internal I/O.
Supplied from power Supply Module
0 to 55 degree
-10 to 75 degree
No condensation 20 to 90 % RH
No condensation 10 to 90 % RH
In accordance with JIS C 0911
Noise voltage 1500 Vpp Noise pulse with 100 ns, 1µs by using
noise simurator.
Based on NEMA ICS 3-304 (with the exception of input module)
Static noise : 3000 V at metal exposed area
250 V DC between External signal terminal and FE terminal
5 V DC 600 mA
No corrosive gasses, no excessive dirt
Attaches to an open wall
Natural air cooling
2/CPU (slot 0 – 2 )
Up to 124 slaves
256 words
256 words
LINK
9.6
Max segment length
19.2
45.45
93.75
187.5
500
1500
3
6
12
System ROM/RAM check,
watch-dog timer check
File name : Hms_1004.gsd
This file can either be downloaded from the webpage
http://www.hms.se/fbfiles.htm
or received by contacting HMS Fieldbus AB.
Please buy the configurator from HMS Fieldbus AB.
Order number: KONF-PDP
Chapter 2 STRUCTURE and SPECIFICATION
Specification
1)
kbps
:
kbps
:
kbps
:
kbps
:
kbps
:
kbps
:
kbps
:
Mbps
:
Mbps
:
Mbps
:
2-2
1200 m
1200 m
1200 m
1200 m
1000 m
400 m
200 m
100 m
100 m
100 m