Technical specifications

10.4 Pneumatic data

Digital output (DQ), terminals 31 and 32
Signal status High
Signal status Low
The status is also Low if the device is faulty or analog input (AI)
is = 0 mA.
10.3

Rated conditions

Rated conditions
Ambient conditions for operation according to IEC 60068-2
● Ambient temperature
● Relative humidity
Pollution degree according to IEC 61010-1
Overvoltage category according to IEC 61010-1
Enclosure degree of protection
● In accordance with IEC 60529
● 6DR711* in accordance with UL 50E
Vibration resistance
● Harmonic oscillations (sine) according to
IEC 60068-2-6
● Bump (half-sine) according to
IEC 60068-2-27
● Noise (controlled digitally) according to
IEC 60068-2-64
10.4
Pneumatic data
Pneumatic data
Pneumatic operating medium
● Operating pressure
Quality class compressed air according to ISO 8573-1
● Solid impurities
● Pressure dew point
● Oil content
Flow rate
● Aerate process drive
38
Conductive, maximum terminal voltage 3 V
Blocked, I < 60 µA
For use indoors and outdoors.
-20 ... +80 °C (-4 ... +176 °F)
0 ... 100%
2
II
IP66
Type 4X
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axle
98.1 m/s² (321.84 ft/s²), 27 ... 300 Hz, 3 cycles/axle
150 m/s² (492 ft/s²), 6 ms, 1000 shocks/axle
10 ... 200 Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz)
200 ... 500 Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz)
4 hours/axle
Compressed air, carbon dioxide (CO
gases
1.4 ... 7 bar (20.3 ... 101.5 psi)
Class 3
Min. 20 C (36 °F) below ambient temperature
Class 3
Operating Instructions, 11/2019, A5E45863537-AC
), nitrogen (N
), noble
2
2
SIPART PS100