Siemens SIPART PS100 Operating Instructions Manual page 28

Electropneumatic positioners
Table of Contents

Advertisement

Parameter assignment and addressing
7.3 SETUP [02]
28
DIRECTION
*) 29
CLOSE TYPE
*) 30
CLOSE LIMIT
*) 31
OPEN TYPE
*) 32
OPEN LIMIT
*) 33
DBAND LIMIT
*) 34
DBAND VALUE
35
LEAKAGE COMP
36
MOUNTING
*) Visible when "AUTO" is selected in "QUICK START [01] > APPLICATION [07]".
28
Meaning
AUTO
Sets the operating direction of the valve defined during initialization.
INVRT
Inverts the operating direction of the valve defined during initialization.
FAST
Sets the valve to a fast response at endstop.
TIGHT
Sets the valve to behavior with maximum actuating force at endstop.
SLOW
Sets the valve to precise behavior at endstop.
LIMIT
Limits the control range to the value set in parameter "CLOSE LIMIT"
[30].
0.0 ... 100.0
Sets the value in % from which the valve closes.
FAST
Sets the valve to a fast response at endstop.
TIGHT
Sets the valve to behavior with maximum actuating force at endstop.
SLOW
Sets the valve to precise behavior at endstop.
LIMIT
Limits the control range to the value set in parameter "OPEN LIMIT" [32].
0.0 ... 100.0
Sets the value in % from which the valve opens.
0.1 ... 3.0
Sets the maximum range of the deadband in %.
x.x
Displays the current value of the deadband.
ON
Enables the leakage compensation.
OFF
Disables the leakage compensation.
AUTO
Sets the positioner to mounting to standard actuator.
LEVER
Sets the positioner to mounting on linear actuator, carrier pin mounted
on lever.
STEM
Sets the positioner to mounting to linear actuator, carrier pin mounted on
spindle.
TURN
Sets the positioner to mounting to part-turn actuator.
Operating Instructions, 11/2019, A5E45863537-AC
SIPART PS100