ABB PVS-60-TL-US Product Manual page 153

Table of Contents

Advertisement

- Error code
- Error message
Name of Alarm and Cause
- Warning
- W012
Battery Low:
- Batt. Low
The inverter has detected a backup battery voltage
-
Flashing yellow
that is too low.
LED
Clock Fail:
- W013
The alarm occurs when there is a difference of
- Clock Fail
more than 1 minute in the time shown the internal
-
Flashing yellow
webserver compared to the internal time of the
LED
microprocessors and indicates a malfunction of the
clock circuit.
- W015
Disconnection due to Anti-Islanding:
- Island Detect.
The inverter has been improperly connected to an
-
Yellow LED
island grid.
- W017*
- String Err.
-
Flashing yellow
Error recorded in measuring string currents:
LED
Damaged string protection fuse(s)
* (only for models with
monitored string fuses)
- W018 *
- SPD DC Err
Intervention of overvoltage surge arresters on DC
-
Flashing yellow
side:
LED
Overvoltage surge arresters situated on the DC side
* (only for models with
are damaged.
monitored SPD)
- W019 *
- SPD AC Err
Intervention of overvoltage surge arresters on AC
-
Flashing yellow
side:
LED
Overvoltage surge arresters situated on the AC side
* (only for models with
are damaged.
monitored SPD)
W021
Activation of reduction in power:
- P-reductionStart
Indicates that one of the power limitations described in
-
No LED
the paragraph "Power limitation messages" has been
triggered.
- W022
Variation in means of managing reactive power:
- Reactive power
Variation in the means of managing reactive power;
mode changed
this change can be made through the internal
-
No LED
webserver.
- W023
Variation in the inverter's date and time:
- date/time changed
Variation of the inverter's date and time; this change
-
No LED
can be made through the internal webserver.
Zeroing of the statistical energy data memorised
- W024
in the EEPROM:
- Energy data reset
Reset of the energy data saved in the inverter;
-
No LED
this operation can be handled through the internal
webserver.
Solution
• Check that the date/time are set correctly and, if they are not,
set them.
Subsequently arrange to completely switch off the inverter (on
both AC and DC) and wait a few minutes.
Finally, restart the inverter and check whether the date/
time are now correctly set or whether they have reset to
01/01/2000. In this case replace the battery with the inverter
completely switched off (isolate AC and DC side) being careful
to maintain the polarity
• Error inside the inverter and cannot be checked externally.
- If the alarm repeats persistently, contact customer
assistance.
• Check that the grid to which the inverter is connected is not
an island grid.
- If the grid to which the inverter is connected is an island
grid, switch the inverter off and then on again: if the problem
persists, contact customer assistance.
• Check with a multimeter the state of the fuses (positioned on
the fuse boards).
- If one or more fuses is open, arrange to replace them and
check that the input current on the string(s) does not exceed
the rating of the fuses (should parallel strings have been made
outside the inverter).
- If there are no damaged string fuses and the inverter
continues to show the alarm message check whether the
settings to be made via the internal webserver are correct
(presence or absence of one or more input strings).
• Observe the inspection window on each surge arrester
(DC side). If it is red, the surge arrester is damaged and the
cartridge must be replaced.
- If the alarm status persists, even if all the surge arresters
have a green inspection window, contact customer assistance.
• Observe the inspection window on each surge arrester
(AC side). If it is red, the surge arrester is damaged and the
cartridge must be replaced.
- If the alarm status persists, even if all the surge arresters
have a green inspection window, contact customer assistance.
• Check which power limitation code is active and, on the
basis of that, carry out the necessary checks that might relate
to various factors including:
- settings by the user
- high grid frequency
- high grid voltage
- anti-islanding
- low grid voltage
- high internal temperature
- high input voltage
The variation in the means of managing reactive power is
done directly by the customer/installer and is not an error. The
information is only saved on the historic record of the events
memorised by the inverter
• The variation in the inverter's date and time is done directly
by the customer/installer and is not an error. The information is
only saved on the historic record of the events memorised by
the inverter
The zeroing of the partial energy values memorised by the
inverter is done directly by the customer/installer and is not an
error. The information is only saved on the historic record of
the events memorised by the inverter
• The warning may also occur when the Memory Card on
which the production statistics are saved is replaced
- 153 -