ABB PVS-60-TL-US Product Manual page 143

Table of Contents

Advertisement

6. Operations on Internal DC disconnect switch(if present)
• Open the internal DC switch
• Affix designated lock preventing operation onto DC disconnect
switch
• Check on the status LEDs
carried out (Missing DC voltage status): All LEDs OFF.
The time needed for the complete shut-down of the LEDs depends by the input voltage of the
inverter. The complete shut-down of the LEDs may require some minutes.
(blue in the below picture).
15
, affixing designated tags (LOTO procedure).
15
the shutdown command has been
05
- 143 -