For the configurable relay operating mode "Alarm Conf.", the following considerations are
valid:
If the alarm condition is persistent, the alarm contact cyclically switches from its resting state
to its activated state.
In the presence of W002 signalling (Input UV – input voltage below the limit of operation),
the alarm contact switches to then reset itself at the end of the alarm signal. This means that
during the reduced input voltage (display message "Waiting Sun") the alarm contact remains
in its resting position.
In the presence of W003, W004, W005, W006, W007 signalling, the alarm contact switches
to then reset itself at the end of the alarm signal. This means that during the absence of grid
voltage (display message "Missing Grid") the alarm contact remains in its resting position.
Vin > Vstart
N.C.
Relay State: Switched
N.O.
Vin < Vstart
N.C.
Relay State: Idle
N.O.
GRID RECONNECTION
t=based on Country Standard
N.C.
Relay State: Idle
N.O.
Vin
Yes
No
IS STILL LESS THAN
Vstart
INVERTER RUN
N.C.
Relay State: Idle
N.O.
ERROR OCCURENCY
ERROR MESSAGE
t=15s
N.C.
Relay State: Switched
N.O.
GRID RECONNECTION
t=based on Country Standard
N.C.
Relay State: Switched
N.O.
ERROR
Yes
No
STILL
PRESENT
• Alarm-Contact (crepuscolar):
The relay is activated (status: switched) as soon as the inverter input
voltage exceeds the activation voltage set.
The relay switch to rest position when the input voltage drops below 70%
of the activation voltage set.
This mode is useful for disconnecting any output transformers that could
have unnecessary consumption during the night.
• Alarm-Contact (alarm ALL - latch):
The relay is activated (status: switched) whenever an error (code Exxx)
or a warning (code Wxxx) is present. When the inverter returns to the
normal operating state and reconnects with the grid, the contact returns
to its position of rest.
Selectable alarms for which the relay is activated
E001
E002
E007
E010
E017
E018
E023
E025
E034
E036
E077
E078
W004
W005
W017
W046
If the alarm condition is persistent, the relay will remain activated (sta-
tus:switched)
- 131 -
E003
E004
E005
E011
E013
E014
E019
E020
E021
E029
E031
E032
E037
E053
E055
E079
E080
E084
W006
W007
W011
W047
W048
7 - Operation
E006
E015
E022
E033
E075
W002
W015