Application Setup Examples; Gp Tm; Introduction; Application Examples - GE AF-650 GP Design And Installation Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Application Setup Examples

6 Application Setup Examples

6.1 Introduction

The examples in this section are intended as a quick
reference for common applications.
Parameter settings are the regional default values
unless otherwise indicated (selected in
K-03 Regional Settings)
Parameters associated with the terminals and
their settings are shown next to the drawings.
Where switch settings for analog terminals A53 or
A54 are required, these are also shown.

6.2 Application Examples

Table 6.1 Analog Speed Reference (Voltage)
TM
AF-650 GP
Design and Installation Guide
Parameters
Function
Setting
AN-10 Terminal
53 Low Voltage
0.07 V*
AN-11 Terminal
10 V*
53 High Voltage
AN-14 Terminal
0 RPM
53 Low Ref./
Feedb. Value
AN-15 Terminal
1,500 RPM
53 High Ref./
Feedb. Value
* = Default Value
Notes/comments:
DET-767A
AN-12 Terminal
53 Low Current
AN-13 Terminal
53 High Current
AN-14 Terminal
53 Low Ref./
Feedb. Value
AN-15 Terminal
53 High Ref./
Feedb. Value
* = Default Value
Notes/comments:
Table 6.2 Analog Speed Reference (Current)
E-01 Terminal 18
Digital Input
E-07 Terminal 37
Safe Stop
* = Default Value
Notes/comments:
Table 6.3 Start/Stop Command with Safe Stop
Parameters
Function
Setting
4 mA*
20 mA*
0 RPM
1,500 RPM
Parameters
Function
Setting
[8] Start*
[1] Safe Stop
Alarm
6-1
6
6