Application Setup Examples
Figure 6.8
Active Reference and Configuration Mode
The active reference can be either the local reference or
the remote reference.
In F-02 Operation Method, the local reference can be
6
6
permanently selected by selecting [2] Local.
To permanently select the remote reference, select [1]
Remote. By selecting [0] Linked to Hand/Auto (default), the
reference site will depend on which mode is active. (Hand
Mode or Auto Mode).
Figure 6.9
6-10
TM
AF-650 GP
Design and Installation Guide
Figure 6.10
Autokeypad Keys
Hand
Hand → Off
Auto
Auto → Off
All keys
All keys
Table 6.13 Conditions for Local/Remote Reference Activation
H-40 Configuration Mode determines what kind of
application control principle (i.e. speed, torque or process
control) is used when the remote reference is active.
H-45 Local Mode Configuration determines the kind of
application control principle that is used when the local
reference is active. One of them is always active, but both
can not be active at the same time.
DET-767A
F-02 Operation
Active Reference
Method
Linked to Hand/
Local
Auto
Linked to Hand/
Local
Auto
Linked to Hand/
Remote
Auto
Linked to Hand/
Remote
Auto
Local
Local
Remote
Remote