GE AF-650 GP Design And Installation Manual page 146

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Specifications
Control card, USB serial communication
USB standard
USB plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB ground connection is not galvanically isolated from protection ground. Use only an isolated laptop as PC connection to
the USB connector on the adjustable frequency drive.
Relay outputs
Programmable relay outputs
Relay 01 Terminal number
1)
Max. terminal load (AC-1)
on 1-3 (NC), 1-2 (NO) (Resistive load)
1)
Max. terminal load (AC-15)
(Inductive load @ cosφ 0.4)
1)
Max. terminal load (DC-1)
on 1-2 (NO), 1-3 (NC) (Resistive load)
1)
Max. terminal load (DC-13)
(Inductive load)
Relay 02 Terminal number
1)
Max. terminal load (AC-1)
on 4-5 (NO) (Resistive load)
1)
Max. terminal load (AC-15)
on 4-5 (NO) (Inductive load @ cosφ 0.4)
1)
Max. terminal load (DC-1)
on 4-5 (NO) (Resistive load)
1)
Max. terminal load (DC-13)
on 4-5 (NO) (Inductive load)
1)
Max. terminal load (AC-1)
on 4-6 (NC) (Resistive load)
1)
Max. terminal load (AC-15)
on 4-6 (NC) (Inductive load @ cosφ 0.4)
1)
Max. terminal load (DC-1)
on 4-6 (NC) (Resistive load)
1)
Max. terminal load (DC-13)
on 4-6 (NC) (Inductive load)
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
Environment according to EN 60664-1
1)
IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2)
Overvoltage Category II
3)
UL applications 300V AC2A
Cable lengths and cross-sections for control cables
Max. motor cable length, shielded
Max. motor cable length, non-shielded
Maximum cross-section to control terminals, flexible/ rigid wire without cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves with collar
Minimum cross-section to control terminals
1)
For power cables, see 12 Terminal and Applicable Wire.
Control card performance
Scan interval
Control characteristics
Resolution of output frequency at 0–1,000 Hz
Repeat accuracy of Precise start/stop (terminals 18, 19)
System response time (terminals 18, 19, 27, 29, 32, 33)
Speed control range (open-loop)
Speed control range (closed-loop)
Speed accuracy (open-loop)
Speed accuracy (closed-loop), depending on resolution of feedback device
Torque control accuracy (speed feedback)
All control characteristics are based on a 4-pole asynchronous motor
TM
AF-650 GP
Design and Installation Guide
2)3)
Overvoltage cat. II
1)
DET-767A
1.1 (Full speed)
USB type B "device" plug
1-3 (break), 1-2 (make)
240 V AC, 0.2 A
24 V DC, 0.1A
4-6 (break), 4-5 (make)
240 V AC, 0.2 A
24 V DC, 0.1A
240 V AC, 0.2 A
24 V DC, 0.1A
24 V DC 10 mA, 24 V AC 20 mA
overvoltage category III/pollution degree 2
500 ft [150 m]
1,000 ft [300 m]
2
0.0023 in
[1.5 mm
2
0.0016 in
[1 mm
2
0.0008 in
[0.5 mm
0.0004 in
1:100 of synchronous speed
1:1,000 of synchronous speed
30–4,000 rpm: error ±8 rpm
0–6,000 rpm: error ±0.15 rpm
max error ±5% of rated torque
2 Form C
240 V AC, 2A
60 V DC, 1A
400 V AC, 2A
80 V DC, 2A
240 V AC, 2A
50 V DC, 2A
2
]/16 AWG
2
]/18 AWG
2
]/20 AWG
13
13
2
2
[0.25 mm
]/
1 ms
±0.003 Hz
≤±0.1 ms
≤ 2 ms
13-17