Commissioning and Diagnosis
Device-specific diagnosis
Important: The diagnostic alarm must be activated for each module!
The device-specific diagnosis only appears in the diagnostic telegram if you en-
abled the "expanded diagnosis" during parameterization.
from
Byte 13
Byte 14
Byte 15
Byte 16
Byte 17
Figure 5-5
5–12
7
0
0
0
0
0
0
1
0
1
5
: Blocksize of device related diagnosis
H
Code for device related diagnosis
7
0
1
1
Status Type: Statusreport = 1
7
0
1
Slotnumber
7
0
Reserved
7
0
Layout of the device-specific diagnosis
Bit-No.
Bit-No.
Bit-No.
Bit-No.
Bit-No.
DA X0 - X1: Short circuit, Overload
DA X2 - X3: Short circuit, Overload
24 V Closed circuit voltage (US2)
DA Overload, Total Power Supply DA X0 - X7
DE X0 - X3: Short circuit, Overload, Inducer
DE X4 - X7: Short circuit, Overload, Inducer
Distributed I/O Device ET 200R
(4)J31069-D0427-U001-A2-7618