Commissioning and Diagnosis
5.5.3

Manufacturer's ID

Definition
The manufacturer's ID contains a code which describes the type of DP slave.
The manufacturer's ID for the ET 200R distributed I/O device is 80A8
5.5.4

ID-related diagnosis

Definition
The ID-related diagnosis indicates whether an error occurred on the ET 200R.
The ID-related diagnosis starts at byte 6 and contains 2 bytes.
The ID-related diagnosis for the ET 200R is organized as shown below.
Figure 5-3
5–10
7
Byte 6
0
1
0
0
Code for ID related diagnosis
7
Byte 7
Layout of the ID-related diagnosis for ET 200R
0
Bit-No.
0
0
1
0
Size of ID related diagnosis
incl. Byte 6 (= 2 Byte)
0
Bit-No.
1
Entry for ET 200R
(Error)
(4)J31069-D0427-U001-A2-7618
.
H
Distributed I/O Device ET 200R