13 - STANDARD MAINTENANCE

13.9 - Refrigerant volume

It is essential to run the unit in cooling mode to find out whether the charge is correct; this is done by checking the actual subcooling.
Following a slight leak, it will be possible to feel a drop in the refrigerant charge from the initial charge, and this will affect the subcooling 
value obtained at the air-cooled exchanger outlet; it cannot, however, be felt in heating mode.

13.10 - Refrigerant properties

R32 properties
Relative
Satur. temp.
pressure
-20
306
-19
321
-18
337
-17
354
-16
371
-15
388
-14
406
-13
424
-12
443
-11
463
-10
483
-9
503
-8
524
-7
546
-6
568
-5
591
-4
614
-3
638
-2
662
-1
687
0
713
1
739
2
766
3
794
Saturated temperatures (°C) based on the relative pressure (in kPa)
Relative
Satur. temp.
pressure
4
822
5
851
6
881
7
912
8
943
9
974
10
1007
11
1040
12
1074
13
1109
14
1144
15
1181
16
1218
17
1256
18
1295
19
1334
20
1375
21
1416
22
1458
23
1501
24
1545
26
1635
25
1590
27
1682
Relative
Satur. temp.
pressure
28
1730
29
1778
30
1828
31
1878
32
1929
33
1982
34
2035
35
2090
36
2145
37
2202
38
2260
39
2318
40
2378
41
2439
42
2501
43
2565
44
2629
45
2695
46
2762
47
2830
48
2899
49
2969
50
3041
51
3114
Relative
Satur. temp.
pressure
52
3189
53
3264
54
3341
55
3420
56
3500
57
3581
58
3664
59
3748
60
3833
61
3920
62
4009
63
4099
64
4191
65
4284
66
4379
67
4476
68
4575
69
4675
70
4777
49