3. Installation space

3-1. Space requirement

Provide sufficient installation space for product safety.
 Single outdoor unit installation
• When the upper space is open:
When there are obstacles at the rear only.
When there are obstacles at the front only.
• When there is an obstruction in the upper space:
When there are obstacles at the rear and
above.
Max. 500
3-1. Space requirement
100 or more
1,000 or more
1,000 or more
100 or more
- (01-7) -
When there are obstacles at the rear and
sides.
80 or
more
100 or more
When there are obstacles at the front and
rear.
1,000 or more
When there are obstacles at the rear, sides,
and above.
80 or
more
100 or more
Unit: mm
300 or
more
100 or more
Unit: mm
1,500 or
more
300 or
more