Service/Special Operation Functions - Fujitsu Super High Power Series Design & Technical Manual

Split type
Table of Contents

Advertisement

3-15. Service/Special operation functions

Line
Access
7070
S
HP interval
HP time since maintenance
7071
S
Reset? (no, yes)
Cur starts compressor 1/hrs run
7073
S
Reset? (no, yes)
U
Emergency operation
Off: Heat pump functions normally (with boosters if necessary)
7141
On: Heat pump uses the electric boost system or the boiler connection
Use the "On" position only in assist mode or test mode: may result in high power bills
S
Emergency operating function type
Manual: Emergency mode is not active when a fault occurs (Emergency mode = OFF)
7142
Automatic: Emergency mode is active when a fault occurs (Emergency mode = ON)
In "Automatic" position, the energy cost can be onerous if the error is not detected and eliminated
7150
I
Simulation outside temperature
• Maintenance
Maintenance functions can be used as a preventive step for periodically monitoring the installation.
All maintenance functions can be individually activated or deactivated. The controller automatically
generates maintenance messages if the settings defined are either exceeded or fail to be reached.
– HP interval: Defines the maintenance frequency (in months) for the heat pump.
– HP time since maintenance: Displays the time (in months) elapsed since the last mainte-
nance. If the value exceeds the "Heat pump interval" (line 7070), the symbol
and a maintenance message will appear in the Info section:
17: Heat pump maintenance Interval (Priority 6)
This setting can be reset with the associated rights of access.
– Cur starts compressor 1/hrs run: The average number of compressor startups per hour of op-
eration, obtained over a period of 6 weeks. If the value exceeds the "Compressor 1 maximum
startups/hr op" adjusted setting, the symbol
appear in the Info section:
8: Too many compressor 1 startups (Priority 9)
This setting can be reset with the associated rights of access.
3-15. Service/Special operation functions
Function
Line
7070
HP interval
7071
HP time since maintenance
7073
Cur starts compressor 1/hrs run
Setting range or display
---, 1...240 months
0...240 months
0...12
Off, On
Manual, Automatic
-50...50 °C
Function
will be displayed and a maintenance message will
- (03-51) -
Factory
setting
--- months
0months
0
Off
Manual
---
will be displayed
3. Function table