Fujitsu Super High Power Series Design & Technical Manual page 57

Split type
Table of Contents

Advertisement

• Heating circuit 2
Line
Access
1010
U
1012
U
1014
U
1016
S
1020
I
1021
I
1030
I
1040
I
1041
I
1050
S
S
As soon as the room temperature = [Setpoint line 1010 (ex. 20°C) + Room temperature limitation
1060
setpoint line 1060 (ex. 0.5 °C)] > 20.5 °C => The heat pump is stopped. It restarts when the room
temperature falls below the setpoint (in the example, Room temperature < 20.0 °C).
1080
S
1090
S
1091
S
1100
S
1101
S
1130
S
1134
S
I
Off: Early interruption of the current program, program inactive
Operational heating
Heating ready for occupation
1150
Operational heating + ready heating
Ready heating + operational heating
Manual: Manual mode enables you to program your own concrete slab drying time
The function ends automatically after 25 days
I
1151
This function enables you to set the custom concrete slab drying temperature. This temperature
remains fixed. The concrete slab-drying program stops automatically after running for 25 days.
1156
I
1157
I
1200
S
3-4. Heating circuit 1 and 2 functions
Function
Comfort setpoint
Reduced setpoint
Frost protection setpoint
Comfort setpoint maximum
Heating curve slope
Offset of the heating curve
Summer/winter heating limits
Flow temperature setpoint minimum 8...70°C
Flow temperature setpoint
maximum
Room influence
Room temperature limitation
Quick setback
Optimum start control maximum
Optimum stop control maximum
Reduced setpoint increase start
Reduced setpoint increase end
Mixer valve boost
Actuator running time
Floor curing function
Floor curing setpoint manually
(if line 1150 = manual)
Floor curing day current
Floor curing day completed
Operating mode changeover
Setting range or display
Reduced setpoint...Comfort setpoint
maximum
Frost protection setpoint...Comfort
setpoint
4°C...Reduced setpoint
Comfort temperature...35 °C
0.1...4
-4.5...4.5°C
8...30 °C
8...70°C
1...100%
0.5...4°C
Off
Down to reduced setpoint Down to
frost protection setpoint
0...360 min
0...360 min
---, -30...10°C
---, -30...10°C
0...50°C
30...873 sec
0...95°C
0...32
0...32
None, Protection mode, Reduced,
Comfort, Automatic
- (03-13) -
Factory
setting
20°C
19.0°C
8.0°C
28.0°C
0.5
0°C
18°C
17°C
55°C
50%
0.5°C
Off
180 min
30 min
---°C
-5°C
0°C
240 sec
Off
25°C
0
Reduced
3. Function table