Fujitsu Super High Power Series Design & Technical Manual page 15

Split type
Table of Contents

Advertisement

 Outdoor unit installation in multi-row
Single parallel unit arrangement
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no ob-
stacle.
• Height above the floor level should be 50 mm or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation
efficiency.
CAUTION
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain
cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely
cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it
might become difficult to get warm, and it is likely to cause product malfunction. Construct a
canopy and a pedestal, or place the unit on a high stand that is locally installed.
3-1. Space requirement
100 or
more
2,000 or more
600 or more
1,000 or more
- (01-9) -
Multiple parallel unit arrangement
Unit: mm
500 or
more
3,000 or more
600 or more
1,500 or more
3. Installation space