Fujitsu Super High Power Series Design & Technical Manual page 20

Split type
Table of Contents

Advertisement

• Optional part
Part name
External connect kit
¢ Peak cut mode
By performing following on-site work, operation that suppresses the current value can be enabled:
The air conditioner is set to the "Peak cut mode" when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
• Circuit diagram example
Outdoor unit
main PCB
Connector
Red
1
White
2
Black
3
10 m*
Surely insulate with
insulation tape etc.
since this wire is not used.
*: Make the distance from the PCB to the connected unit within 10 m.
– Use following parts and construct like that shown above.
– Input signal: On: Low noise mode, Off: Normal operation
NOTE: Set peak cut mode by pushing the switch on the outdoor unit main PCB.
Input signal
Peak cut mode
• Optional part
Part name
External connect kit
6-1. External input
Model name
UTY-XWZXZ2
Connected unit
Vcc
Vcc
Power
supply
R
SW
Signal
Locally purchased
On
Off
On
Off
Model name
UTY-XWZXZ2
- (01-14) -
External input wire (Red/White/Black)
Power supply
Voltage (chart sign: Vcc): DC 5 to 24 V
Current capacity: About 100 mA
Switch (Chart sign: SW)
Toggle switch or Rocker switch, etc: Switch
which maintains the states.
Prepare switches which are enough capable
for DC 10 mA current or more.
Resistance (Chart sign: R)
Adjust the resistance for current to about 10 mA
In the case of Vcc = DC 5 V: 470 Ω 1/4 W
In the case of Vcc = DC 12 V: 1 kΩ 1/4 W
In the case of Vcc = DC 24 V: 2.2 kΩ 1/4 W
External input wire (Red/White/Black)
Exterior
Exterior