Analog Inputs; Recorded Measured Values; Min/Max Values - Siemens SIPROTEC 7SJ80 Manual

Overcurrent protection, motor protection, voltage and frequency protection
Hide thumbs Also See for SIPROTEC 7SJ80:
Table of Contents

Advertisement

3.5

Analog Inputs

Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 02 (16-Bit Analog Input)
Change Event Variation reported when variation 0 requested:02 (Analog Change Event without Time)
Point In-
Name
dex
3.5.1

Recorded measured values

0
la=
1
lb=
2
lc=
3
I0=
4
Va=
5
Vb=
6
Vc=
7
Va-b=
8
Vb-c=
9
Vc-a=
10
V=
11
P=
12
Q=
13
S=
14
Freq=
15
cos
φ
=
16
UsrMv1
17
UsrMv2
18
UsrMv3
19
UsrMv4
20
UsrMv5
21
UsrMv6
22
UsrMv7
23
UsrMv8
24
UsrMv9
25
UsrMv10
26
UsrMv11
27
UsrMv12
3.5.2

Min/Max values

28
la Min=
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
Description
Current phase a
Current phase b
Current phase c
Current I0
Voltage phase a
Voltage phase b
Voltage phase c
Voltage phase a to phase b
Voltage phase b to phase c
Voltage phase c to phase a
Voltage Ground
Active power
Reactive power
Apparent power
frequency
power factor
user defined measurement
user defined measurement
user defined measurement
user defined measurement
user defined measurement
user defined measurement
user defined measurement
user defined measurement
user defined measurement
user defined measurement
user defined measurement
user defined measurement
Current phase a minimum
Scaling(32767 corre-
Default Change
sponds to ...)
Event assigned
3276.7 A
3276.7 A
3276.7 A
3276.7 A
32.767 kV
32.767 kV
32.767 kV
32.767 kV
32.767 kV
32.767 kV
32.767 kV
32767 kW
32767 kVar
32767 kVar
327.67 Hz
3.2767
3276.7
3276.7
3276.7
3276.7
3276.7
3276.7
3276.7
3276.7
3276.7
3276.7
3276.7
3276.7
3276.7 A
Analog Inputs
Class
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
35

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7sk80Siprotec 7rw80

Table of Contents