Binary Inputs / Annunciations; Error With A Summary Alarm; Alarm Summary Event - Siemens SIPROTEC 7SJ80 Manual

Overcurrent protection, motor protection, voltage and frequency protection
Hide thumbs Also See for SIPROTEC 7SJ80:
Table of Contents

Advertisement

Notes to SIPROTEC objects
1.1

Binary Inputs / Annunciations

1.1.1

Error with a summary alarm

Reference
1.1.2

Alarm Summary Event

Reference
10
Note
The description of the standard mappings / point lists (ref. to chap. 3) contains the pre-
allocation of the mapping files at delivery or first assignment of a mapping in DIGSI 4
to the SIPROTEC device.
Changes of the allocation and the scaling of the measured values are possible in ad-
aptation to the concrete installation enviroment (ref. to page 3).
Note
Depending on the device composition and the existing protection packages not all of
the indicated binary inputs or protection annunciations (and corresponding DNP
points) may be available in the SIPROTEC device
The "Error with a summary alarm" is ON if at least one of the following internal alarms
assumes the value ON:
• "Error 5V", "Error neutral CT", "Error 1A/5A wrong", "Error A/D converter".
ref to chap. 3.2.12
The "Alarm summary event" is indicated, if at least one of the following internal alarms
assumes the ON status:
• "Error Board 1", "Error Board 2", "Error Board 3", "Error Board 4", "Error Board 5",
"Error Board 6", "Error Board 7",
• "Alarm NO calibration", "Failure Battery", "Alarm Real Time Clock",
• "Failure Phase Sequence", "VT Fuse Failure", "Failure Voltage Balance", "Failure
Voltage Summation Phase – Ground", "Failure General Voltage Supervision",
• "Failure Current Balance", "Failure Current Summation", "Failure General Current
Supervision".
ret. to chap. 3.2.12
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7sk80Siprotec 7rw80

Table of Contents