3.3
Control Relay Output Blocks/Binary Output Status
Binary Output Status Points
Object Number: 10
Request Function Codes supported: 1 (Read)
Default Variation reported when variation 0 requested: 2 (Binary Output Status)
Control Relay Output Blocks/Binary Output Status
Object Number: 12
Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack)
Point In-
Name
dex
3.3.1
External commands (Double point commands)
0
52Breaker
1
52Breaker
2
Switch 1
3
Switch 1
4
Switch 2
5
Switch 2
6
Switch 3
7
Switch 3
8
Switch 4
9
Switch 4
10
Switch 5
11
Switch 5
12
Switch 6
13
Switch 6
14
Switch 7
15
Switch 7
16
Switch 8
17
Switch 8
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
Description
Trip Breaker switch
Close Breaker switch
Trip switch 1
Close switch 1
Trip switch 2
Close switch 2
Trip switch 3
Close switch 3
Trip switch 4
Close switch 4
Trip switch 5
Close switch 5
Trip switch 6
Close switch 6
Trip switch 7
Close switch 7
Trip switch 8
Close switch 8
Control Relay Output Blocks/Binary Output Status
Supported Control
Relay Output Block
Fields
Trip, Pulse On
1
(On Time Fixed
)
Close, Pulse On
(On Time Fixed)
Trip, Pulse On
(On Time Fixed)
Close, Pulse On
(On Time Fixed)
Trip, Pulse On
(On Time Fixed)
Close, Pulse On
(On Time Fixed)
Trip, Pulse On
(On Time Fixed)
Close, Pulse On
(On Time Fixed)
Trip, Pulse On
(On Time Fixed)
Close, Pulse On
(On Time Fixed)
Trip, Pulse On
(On Time Fixed)
Close, Pulse On
(On Time Fixed)
Trip, Pulse On
(On Time Fixed)
Close, Pulse On
(On Time Fixed)
Trip, Pulse On
(On Time Fixed)
Close, Pulse On
(On Time Fixed)
Trip, Pulse On
(On Time Fixed)
Close, Pulse On
(On Time Fixed)
31