1.800.561.8187
®
AmpFlex
- Flexible AC Current Probes
Specifications
Model
300A
Measurement
5 to 300A
Range
Accuracy
±1% +200mA
Output Signal
10mV/A
Crest Factor
3.0
(mid-range)
Phase Shift
1.5°
@ 50/60Hz
Residual Noise
200mA
Model #
3000A
Measurement
5 to 3000A
Range
Accuracy
±1% +200mA
Output Signal
1mV/A
Crest Factor
3.0
(mid-range)
Phase Shift
0.7°
@ 50/60Hz
Residual Noise
200mA
*Reference Conditions: 25°C ± 5°K, 20 to 75% RH, 1 minute warm-up, battery at 9V ± 0.5V, conductor
center, external DC magnetic field < 40A/m, no external AC magnetic field, no external electrical field, 10
to 100Hz, sine wave. See accuracy curves for low currents.
www.
30/300A
1000A
5 to 300A
5 to 1000A
±1% +200mA
±1% +200mA
100mV/A or
1mV/A
10mV/A
3.0
9.0
1.3°
0.7°
200mA
200mA
300/3000A
3000/30000A
5 to 3000A
5-30000A
±1% +200mA
±1% +1A
10mV/A or
1mV/A or
1mV/A
0.1mV/A
3.0
3.0
0.7°
0.5°
200mA
1A
- 8 -
.com
100/1000A
5 to 1000A
±1% +200mA
10mV/A or
1mV/A
9.0
0.7°
200mA
600/6000A
5 to 6000A
±1% +500mA
1mV/A or
0.1mV/A
> 10
0.5°
500mA