Communication System Manual
3.5.2.4.2 Output data (from PROFIBUS to 3WN6)
The 6 words of input data are divided into the following data areas:
Octet 1
Parameter identifier
Octet 2
Octet 3
Parameter subindex
Octet 4
Reserved
Octet 5
Octet 6
Parameter value
Octet 7
Octet 8
Octet 9
High-order byte of main
control word
Octet 10
Low-order byte of main
control word
Octet 11
High-order byte of main
setpoint
Octet 12
Low-order byte of main
setpoint
The following functions are available in the main control word:
Octet 9: High-order byte of main control word
Bit 15
Bit 14
Bit 13
0
0
0
|
|
|
Octet 10: Low-order byte of main control word
Bit 7
Bit 6
Bit 5
0
0
0
|
|
|
|
|
|
|
|
|
General example:
Set the "z" release setting current to a value of 25 kA.
Enter the following codes in the input area (AW 0 - 6) of the DP/RS 485 interface (3WN6):
DW no.
Value
AW 0
KF= +00782
AW 2
KY= 005,000
AW 4
KY= 022,000
AW 6
KF= +25000
and then enter the request identifier for transferring a value (A 0.4 & A 0.5 = 1, in AW = 0).
62
Profile control
for communication-capable
low-voltage devices
on PROFIBUS-DP (kNS/DP)
Direct control commands
See below
Setting current Ir
Bit 12
Bit 11
Bit 10
0
0
0
|
|
|
Bit 4
Bit 3
Bit 2
0
0
0
|
|
|
|
|
|
|
|
|
Not supported
Meaning
"z" release setting current, parameter identifier
Parameter subindex
Integer data value, conversion factor
corresponds to 25 kA
© Copyright Siemens AG 1998. All rights reserved.
Bit 9
Bit 8
0
|
|
COM_CLEAR bit
Bit 1
Bit 0
|
|
Switch 3WN6 ON
|
Switch 3WN6 OFF
3WN6 Circuit-Breakers
Version 1.0 (02/98)