Communication System Manual

4.5.3 Operation

When you have installed and wired the interface module in accordance with the installation guidelines, you
still have to set the PROFIBUS address before start-up. It is not necessary to set the baud rate as the
interface module automatically synchronizes with the baud rate of the master in the range 9.6 Kbit/s to
12 Mbit/s.
You can check that the interface modules is working properly by checking the display elements on start-up.

4.5.3.1 Operating elements

4.5.3.1.1 Setting the address
The two rotary switches on the front panel of the interface module are used to set the
PROFIBUS address in the range 00 ... 99.
Use the rotary switch on the left labeled "x10" to set the tens for the address.
Use the rotary switch on the right labeled "x1" to set the units.
Fig. 23: Setting the PROFIBUS-DP address
SIEMENS
De vice
Interface
PROFIBUS-DP
Address
0
0
1
9
1
2
8
2
3
7
3
4
6
4
5
5
3RK1002-0BB00-0AA0
x 10
x1
3WN1,3WS1
24V
0V
Note
Transfer of PROFIBUS address
If you set or change the address after switching on the device, you must
!
restart the device as the PROFIBUS address is only read in and transferred
once, i.e. immediately after the device is switched on.
Version 1.0 (02/98)
DP / 3WN 1 ,3WS 1
9
8
7
6
1 2 3 4 5 6
G / 19.04.96
© Copyright Siemens AG 1998. All rights reserved.
3WN1, 3WS1 Circuit-Breakers
Address
0
0
9
1
9
1
8
2
8
2
7
3
7
3
6
4
6
4
5
5
x 10
x 1
101