3.4.2 List of acyclic 3WN6 messages on PROFIBUS-DP

Message group 0
M.
Designation
no.
0:x
Circuit-breaker
key data
Note: Circuit-breaker key data, i.e. messages 0:1 to 0:21 are "read only" data.
x =
1
Test unit + delivery
date
2
Identifier number
4
Rated current of
circuit-breaker
5
Function test of
release
11
Circuit-breaker size
12
Circuit-breaker
type
13
No. of poles
14
Version of release
unit (in ASCII
code)
15
Revision level of
communication
16
Communication
module version
17
Revision level of
release unit
21
Communication
address
17)
The message addresses are shown as decimal numbers in the following; input must be in binary format.
18)
The value ranges shown here and on the following pages are transferred in the corresponding binary format.
19)
0: System 0K; 1: Bus error; 2: CT recognition module error; 3: LCD error.
20)
11: Communication functions (Z=F01 in order number); 91: Communication and measurement functions (Z=F05)
21)
Not supported at present.
Version 1.0 (05/98)
Message
Value range
18)
address
17)
Releases
N and P
500, 1, 0, 0, 0
1 - 111194
500, 2, 0, 0, 0
0 - 99
500, 4, 0, 22, 0
315 - 3200 A
500, 5, 0, 0, 0
0 - 3
502, 1, 0, 0, 0
1 - 2
502, 2, 0, 0, 0
2
502, 3, 0, 0, 0
3 - 4
502, 4, 0, 0, 0
"N" or "P"
(ASCII code)
502, 5, 0, 0, 0
(2 bytes:
hardware +
software)
502, 6, 0, 0, 0
11; 91
502, 7, 0, 0, 0
(2 bytes:
hardware +
software)
)
21
503, 1, 0, 0, 0
© Copyright Siemens AG 1998. All rights reserved.
Value range
18)
Releases
H and J/K
-
-
315 - 3200 A
)
19)
19
0 - 3
-
-
-
"H" or "J"
(ASCII code)
(2 bytes:
hardware +
software)
)
20)
20
11
(2 bytes:
hardware +
software)
21)
3WN6 Circuit-Breakers
Value range
18)
Releases
D and E/F
-
-
315 - 3200 A
19)
0 - 3
-
-
-
"D" or "E"
(ASCII code)
(2 bytes:
hardware + software)
20)
11
(2 bytes:
hardware + software)
21)
39